Gauge Pressure Transmitter EJA430A

Gauge Pressure Transmitter EJA430A is used to measure the pressure of liquids, gases or vapors. It supports BRAIN\\HART and FOUNDATIONTM fieldbus or PROFIBSUS PA communication protocols. It uses monocrystalline silicon resonant sensor technology.

Send InquiryChat Now
Gauge Pressure Transmitter EJA430A

Gauge Pressure Transmitter EJA430A


Feature :

Gauge Pressure Transmitter EJA430A is used to measure the pressure of liquids, gases or vapors. It supports BRAIN\\HART and FOUNDATIONTM fieldbus or PROFIBSUS PA communication protocols. It uses monocrystalline silicon resonant sensor technology. Monocrystalline silicon is an ideal material for the absence of hysteresis in pressure or temperature changes. Monocrystalline silicon resonant sensors minimize the effects of overvoltage, temperature and static pressure, providing unmatched long-term stability.



Installation precautions:

1. Before starting, if the valve is closed, the valve should be opened very carefully and slowly when used, so as not to damage the diaphragm of the transducer by direct impact of the detected medium.


2. The pipe must be kept clean. The sediment in the pipe will pop out and damage the diaphragm of the transmitter.


3. Do not leak air when the transmitter and heat pipe are out.


4. During installation, take the pressure opening of oil tank (or other) as low as possible to eliminate the error caused by temperature change and introduce temperature compensation if necessary.


5. When oil tanks (or other tanks) are not equal in level (such as small or large), compensation measures should be considered. For example, professional instrument level adjustment device can be used in the secondary table.


6. In order to achieve the accuracy of use, for example, when the breathing valve is installed on the top of the oil tank, the differential pressure transmitter must be used instead of the pressure transmitter.


7. When remote transmission needs secondary display instruments, professional intelligent digital display meters should be selected as far as possible, which can change the range and realize temperature compensation.



Specification :


Output 

Two wire 4 to 20 mA DC output with digital communications. BRAIN or HART FSK protocol are superimposed on

the 4 to 20 mA signal.


Failure Alarm

Output status at CPU failure and hardware error;

Up-scale: 110%, 21.6 mA DC or more(standard)

Down-scale: -5%, 3.2 mA DC or less 

-2.5%, 3.6 mA DC or less (Optional code /F1)



Stability

0.1 % of URL per 60 months


Power Supply Effects

0.005 % per Volt (from 21.6 to 32 V DC, 350 )



Ambient Temperature Limits

(approval codes may affect limits)

-40 to 85 C (-40 to 185 F)

-30 to 80 C (-22 to 176 F) with LCD Display


Process Temperature Limits

(approval codes may affect limits)

-40 to 120 C (-40 to 248 F)


Ambient Humidity Limits

5 to 100 % RH @ 40 ℃ (104℉)



Supply & Load Requirements

(Safety approvals can affect electrical requirements)

With 24 V DC supply, up to a 570  load can be used. See Figure 2.


Supply Voltage

10.5 to 42 V DC for general use and flameproof type

10.5 to 32 V DC for lightning protector (Optional code /A)

10.5 to 30 V DC for intrinsically safe, Type n, nonincendive, or non-sparking type

Minimum voltage limited at 16.4 V DC for digital communications, BRAIN and HART


Order information :