E-mail: newsales12@vip.163.com
Tel: +86-15829050512

Rosemount 3144P Temperature Transmitter

Rosemount 3144P Temperature Transmitter has a dual-chamber housing that ensures reliability and advanced diagnostics to keep your measurement points up and running. It is equipped with a single sensor and dual sensor inputs so it can receive inputs from two independent sensors simultaneously.

Send Inquiry
Rosemount 3144P Temperature Transmitter

Rosemount 3144P Temperature Transmitter


Rosemount 3144P Temperature Transmitter has a dual-chamber housing that ensures reliability and advanced diagnostics to keep your measurement points up and running. It is equipped with a single sensor and dual sensor inputs so it can receive inputs from two independent sensors simultaneously. Dual sensor configurations can be used to balance temperature, measure temperature differences, perform redundant temperature measurements, and use important functions such as hot backup and sensor drift alarms.


Feature :

The industry-leading Rosemount 3144P Single Point temperature transmitter delivers unmatched field reliability and innovative process measurement solutions and diagnostics Transmitter features include:

• Dual and Single Sensor Input Capabilities
• Transmitter-Sensor Matching (Option Code C2)
• Integral Transient Protector (Option Code T1)
• IEC 61508 Safety Certificate of Compliance (Option Code QT)
• Advanced Sensor and Process Diagnostics (Option Codes D01 and DA1)
• Large, Easy to Read LCD Display (Option Code M5)
• Assemble to Sensor” option (Option Code XA)

 

Specification :

Inputs

User-selectable. See Table 2 on page 8 for sensor options.

Output

2-wire device with either 4–20 mA/HART, linear with temperature or input, or completely digital output with FOUNDATION fieldbus communication (ITK 5.0.1 compliant).

Isolation

Input/output isolation specified to 500 Vdc (500 Vrms 707 V peak) at 50/60 Hz.

Humidity Limits

0–99% relative humidity.

Update Time

Approximately 0.5 seconds for a single sensor (1 second for dual sensors).

Physical Specifications

Conduit Connections

The standard field mount housing has ½–14 NPT conduit entries.

Additional conduit entry types are available, including PG13.5 (PG11), M20 X 1.5 (CM20), or JIS G ½. When any of these additional entry types are ordered, adapters are placed in the standard field housing so these alternative conduit types fit correctly. See “Dimensional Drawings” on page 18 for dimensions.

Materials of Construction

Electronics Housing

• Low-copper aluminum or CF-8M (cast version of 316 Stainless Steel)

Paint

• Polyurethane

Cover O-rings

Buna-N

Mounting

Transmitters may be attached directly to the sensor. Optional mounting brackets (codes B4 and B5) allow for remote mounting.

See “Optional Transmitter Mounting Brackets” on page 19


Enclosure Ratings

Type 4X

IP66 and IP68

Stability

• RTDs: - ±0.1% of reading or 0.1 °C, whichever is greater, for 24 months.

• Thermocouples: - ±0.1% of reading or 0.1 °C, whichever is greater, for 12 months.

5 Year Stability
• RTDs: - ±0.25% of reading or 0.25 °C, whichever is greater, for 5 years.
• Thermocouples: - ±0.5% of reading or 0.5 °C, whichever is greater, for 5 years.

 